Advantech RS-485 Manual do Utilizador Página 199

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
Vista de página 198
ADAM-5000 6-77
Chapter 6
$aaSiCjAhEs $aaSiCjAhEs
Example command: $03S0C1ALEE(cr)
response: !03(cr)
Channel 1 of slot 0 in the ADAM-5000 system at
address 03h is instructed to enable its Low alarm
function.
The module confirms that its Low alarm function has
been enabled.
Note: An analog input module requires a maximum of 2
seconds after it receives an Enable/Disable Alarm
command to let the setting take effect. During this
interval, the module cannot be addressed to perform
any other actions.