Advantech Data Acquisition Modules ADAM 4000 Manual do Utilizador Página 185

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 429
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 184
Chapter 5
5-39
ADAM 4000 Series User’s Manual
4018M
@AAT
Name Read Memory Operation Mode command
Description Request the memory operation status of the analog input
data logger at address AA.
Syntax @AAT (cr)
@ is a delimiter character.
AA (range 00-FF) represents the 2-character hexadecimal
address of an analog input data logger.
T is the Read Memory Operation Mode command.
(cr) is the terminating character, carriage return (0Dh).
Response !AAO(cr) if the command is valid.
! is a delimiter character indicating a valid command was
received.
AA (range 00-FF) represents the 2-character hexadecimal
address of an analog input module.
O represents the operation mode:
‘1’: enables the recording of data.
‘0’: disables the recording of data.
(cr) is the terminating character, carriage return (0Dh).
Example command: @F3T(cr)
response: !F31(cr)
The command requests the memory operation status of the
analog input data logger at address F3.
The response indicates that data recording is enabled.
Vista de página 184
1 2 ... 180 181 182 183 184 185 186 187 188 189 190 ... 428 429

Comentários a estes Manuais

Sem comentários