Advantech Data Acquisition Modules ADAM 4000 Manual do Utilizador Página 282

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 429
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 281
Chapter 7
7-
47
ADAM 4000 Series User’s Manual
$AA6N
Name Clear Counter command
Description Clears the counter 0 or counter 1 of the specified
counter/frequency module.
Syntax $AA6N(cr)
$ is a delimiter character.
AA (range 00-FF) represents the 2-character hexadecimal
address that you will access to.
6 is the Clear Counter command.
N determines the counter which should be cleared.
N = 0 represents counter 0
N = 1 represents counter 1
(cr) is the terminating character, carriage return (0Dh).
Response !AA(cr) if the command is valid.
There is no response if the module detects a syntax or
communication error, or even if the specified address does
not exist.
! is a delimiter character which indicates a valid command.
AA (range 00-FF) represents the 2-character hexadecimal
address of the module.
(cr) is the terminating character, carriage return (0Dh).
Example command: $1361(cr)
response: !13(cr)
The command requests the counter/frequency module at
address 13 to clear counter 1. The module replies with its
address indicating that the counter has been cleared.
4080, 4080D
Vista de página 281
1 2 ... 277 278 279 280 281 282 283 284 285 286 287 ... 428 429

Comentários a estes Manuais

Sem comentários