Advantech Data Acquisition Modules ADAM 4000 Manual do Utilizador Página 46

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 429
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 45
Chapter 3
Chapter 3 I/O Modules
3-19
Technical specification of ADAM-4015
Channel Number 6 differential
Support Protocol ADAM ASCII and MODBUS/RTU
Input Type Pt100, Pt1000, BALCO500, Ni
Input Connections 2 or 3 wires
Wire Burnout Detection Yes
Input Type and
Temperature Range
Pt100: -50 to 150° C
0 to 100° C
0 to 200° C
0 to 400° C
-200 to 200° C
Pt1000: -40 to 160° C
Balco500: -30 to 120° C
Ni 50 RTD: -80 to 100° C
Ni 508 RTD: 0 to 100° C
Isolation Voltage 3000 V
DC
Sampling Rate 10 sample/second (total)
Input Impedance 10 M
Resolution 16-bit
Accuracy ±0.1% or better
CMR@50/60Hz 120 dB
NMR@50/60Hz 100 dB
Span Drift
± 25 ppm/
Zero Drift
± 3 V/
Watchdog Timer System (1.6 second) and Communication
Power Input +10~+30 V
DC
(non-regulated)
Power Consumption 1.2 W @ 24V
DC
Table 3-1 Technical specification of ADAM-4015